Installation wire PVZ

  • materialcopper (PV)
  • section0.5–400 sq.mm
  • materialpolyvinyl chloride plastic

Description

Application

Designed for installation of sections of electrical circuits where wire bends are possible.

 

Design features

Section, sq.mm Wire resistance, no more than Ohm/km Cable outer diameter, mm Weight of 1 km of cable, kg
0,5 40,500 2,1 9
0,75 26,000 2,5 12
0,75 26,000 2,3 11
1 19,500 2,5 14
1 19,500 2,4 13
1,5 13,300 3,0 21
1,5 13,300 2,9 19
2,5 7,980 3,7 34
4 4,950 4,3 49
6 3,110 5,2 73
10 9,320 6,0 111
10 9,230 6,3 118
16 15,300 8,3 172
25 0,809 10,4 258
35 0,551 12,0 367
50 0,394 13,4 496
70 0,277 16,3 673
95 0,203 18,2 936
120 0,161 19,6 1158
150 0,130 22,4 1444
185 0,105 24,5 1768
240 0,080 28,0 2316
300 0,065 33,0 2864
400 0,050 35,9 3729

 

Technical specifications

Диапазон температур эксплуатации

Operating temperature range

from -40 °C to +50 °C

in the HL version — from -60˚C to +50 °C

 

Относительная влажность воздуха

Relative air humidity

at temperatures up to 35 °C up to 98%

 

Прокладка и монтаж кабелей без предварительного подогрева производится при температуре не ниже

Laying and installation of cables without preheating is carried out at a temperature not lower than

-15 °C

 

Длительно допустимая температура нагрева жил кабелей при эксплуатации

Long-term permissible heating temperature of cable cores during operation

+70 °C

 

Минимальный радиус изгиба при прокладке

Minimum bending radius during installation

5 external diameters

Гарантийный срок эксплуатации — 2 года

Warranty period of operation — 2 years

Service life — 15 years

Certificate of Conformity

GOST 6323-79

TU BY 300528652.004-2004