1. Round single-wire conductive core
- Material: aluminum (A), copper;
- Cross-section (aluminum):
- Number of cores 4; 5; 7; 10; 14; 19; 27; 37; 52; 61; — 2.5 sq.mm;
- Number of cores 4; 5; 7; 10; 14 — (4–10) sq.mm;
- Cross-section (copper):
- Number of cores 4; 5; 7; 10; 14; 19; 27; 37; 52; 61; — (0.75–2.5) sq.mm;
- Number of cores 4; 5; 7; 10; 14; — (4–10) sq.mm.
2. Insulation
Made of polyvinyl chloride plastic (V) or cross-linked polyethylene (PV).
3. Twisting
The insulated cable cores are twisted into a layer, each layer has a counting pair, the insulated cores of which differ in color from each other and from the rest of the cores, the color of the insulation of which must be the same.
4. Inner filling (belt insulation)
- for cables (A)KVVGz made of PVC plastic;
- for cables with armor or screen (A)KVVGE, (A)KVBbShv, (A)KVBShv, (A)KVKShv, (A)KPvVGE, (A)KPvBbShv, (A)KPvBShv, (A)KPvKShv, (A)KVBShp,
- (A)KVKShp, (A)KVKShp — made of PVC plastic compound or applied by winding or longitudinally with tapes made of polyvinyl chloride plastic compound.
5. Screen
For cables (A)KVVP (A)KPvVG made of two copper tapes or copper foil, or aluminum foil with overlap, copper wire must be laid along the aluminum foil.
6. Armor
- for cables (A)KVBbShv, (A)KVBShv, (A)KPvBbShv, (A)KPvBShv, (A)KVBShp, (A)KPvBShp — made of two galvanized steel tapes;
- for cables (A)KVKShv, (A)KPvKShv, (A)KVKShp, (A)KPvKShp — made of galvanized steel wires;
- for cables (A)KVKaShv, (A)KPvKaShv, (A)KVKaShp, (A)KPvKaShp — made of aluminum wires or aluminum alloy wires.
7. Sheath
Made of polyvinyl chloride plastic compound (v) or 3 polyethylene (p).
Application
Cables are intended for laying indoors, in canals, tunnels, in aggressive environments, in the absence of mechanical impacts on the cable. Laying in the ground (trenches) is allowed, providing protection of cables at the points of exit to the surface. Fire hazard class according to GOST 31565-2012 O1.8.2.5.4
Design features
| Section, sq.mm | Wire resistance, no more than Ohm/km | O.D. | Weight of 1 km of cable, kg | ||
| Al | Cu | АКVVG | КVVG | ||
| 4×0,75 | - | 24,500 | 7,6 | - | 78 |
| 5×0,75 | - | 24,500 | 8,3 | - | 92 |
| 7×0,75 | - | 24,500 | 9,5 | - | 134 |
| 10×0,75 | - | 24,500 | 11,7 | - | 176 |
| 14×0,75 | - | 24,500 | 12,6 | - | 225 |
| 19×0,75 | - | 24,500 | 13,9 | - | 287 |
| 27×0,75 | - | 24,500 | 16,3 | - | 391 |
| 37×0,75 | - | 24,500 | 18,6 | - | 527 |
| 52×0,75 | - | 24,500 | 21,6 | - | 713 |
| 61×0,75 | - | 24,500 | 22,9 | - | 819 |
| 4×1 | - | 18,100 | 8,0 | - | 91 |
| 5×1 | - | 18,100 | 9,3 | - | 121 |
| 7×1 | - | 18,100 | 10,0 | - | 158 |
| 10×1 | - | 18,100 | 12,3 | - | 209 |
| 14×1 | - | 18,100 | 13,3 | - | 269 |
| 19×1 | - | 18,100 | 14,7 | - | 346 |
| 27×1 | - | 18,100 | 17,3 | - | 473 |
| 37×1 | - | 18,100 | 19,7 | - | 639 |
| 52×1 | - | 18,100 | 23,0 | - | 869 |
| 61×1 | - | 18,100 | 24,8 | - | 1024 |
| 4×1,5 | - | 12,100 | 9,2 | - | 127 |
| 5×1,5 | - | 12,100 | 10,0 | - | 154 |
| 7×1,5 | - | 12,100 | 10,7 | - | 200 |
| 10×1,5 | - | 12,100 | 13,3 | - | 266 |
| 14×1,5 | - | 12,100 | 14,4 | - | 348 |
| 19×1,5 | - | 12,100 | 15,9 | - | 451 |
| 27×1,5 | - | 12,100 | 19,3 | - | 639 |
| 37×1,5 | - | 12,100 | 21,5 | - | 842 |
| 52×1,5 | - | 12,100 | 25,5 | - | 1174 |
| 61×1,5 | - | 12,100 | 27,0 | - | 1355 |
| 4×2,5 | 12,100 | 7,410 | 10,2 | 111 | 173 |
| 5×2,5 | 12,100 | 7,410 | 11,0 | 135 | 213 |
| 7×2,5 | 12,100 | 7,410 | 11,9 | 167 | 282 |
| 10×2,5 | 12,100 | 7,410 | 14,9 | 221 | 377 |
| 14×2,5 | 12,100 | 7,410 | 16,1 | 281 | 499 |
| 19×2,5 | 12,100 | 7,410 | 12,9 | 357 | 653 |
| 27×2,5 | 12,100 | 7,410 | 21,7 | 505 | 927 |
| 37×2,5 | 12,100 | 7,410 | 24,7 | 676 | 1255 |
| 4×4 | 7,410 | 4,610 | 11,8 | 150 | 250 |
| 7×4 | 7,410 | 4,610 | 14,0 | 232 | 418 |
| 10×4 | 7,410 | 4,610 | 17,6 | 309 | 560 |
| 4×6 | 5,110 | 3,080 | 13,0 | 185 | 334 |
| 7×6 | 5,110 | 3,080 | 15,5 | 293 | 571 |
| 10×6 | 5,110 | 3,080 | 20,0 | 409 | 784 |
| 4×10 | 3,080 | 1,830 | 15,9 | 276 | - |
| 7×10 | 3,080 | 1,830 | 19,5 | 468 | - |
| 10×10 | 3,080 | 1,830 | 25,3 | 648 | - |
Technical specifications
-
Operating temperature range
from -50°C to +50°C (PVC sheath)
from -60°C to +50°C (PE sheath)
Relative air humidity
at temperatures up to 35°C up to 98%
Laying and installation of cables without preheating is carried out at a temperature not lower than
-15 °C (PVC sheath)
-20 °C (PE sheath)
Minimum bending radius during installation
at ambient temperature not lower than 0 °C:
- for cables with an outer diameter up to 10 mm inclusive — 3 outer diameters
- for cables with an outer diameter over 10 mm to 25 mm inclusive — 4 outer diameters
without preheating at ambient temperature not lower than -15 °C — 6 outer diameters
without preheating at ambient temperature not lower than -7 °C — 10 outer diameters
Nominal frequency
50 Hz
Test alternating voltage with a frequency of 50 Hz
for a voltage of 0.66 kV — 3 kV
Long-term permissible heating temperature of cable cores during operation
+70 °C (PVC insulation)
+90 °C (PE insulation)
Warranty period of operation — 5 years
Service life — 30 years
Certificate of Conformity
GOST 1508-78 TU BY 300528652.008-2008
GOST 1508-78
TU BY 300528652.021-2010
TU BY 300528652.042-2015